CABLE MINIMUM INSTALLED BENDING RADII

TypeVoltageFactor Instal.Factor During instal.
Fixed Wiring PVC or Elastomer or XLPE
(1) Single and Multicore
(a) Overall diameter to & including 25mm 0.6/1kV 4 6
(b) Overall diameter over 25mm 0.6/1kV 6 9
(2) Multicore SWA or metal tape 0.6/1kV 12 18
(3) Solid Aluminium, compacted or sector 0.6/1kV 8 12
Flexible Cords PVC or Elastomer 250/440V 4
0.6/1kV 4
Flexible Cables PVC or Elastomer (incl. Versolex®) 0.6/1kV 4
Lead Sheath PVC or Elastomer 0.6/1kV 12 18
Paper Insulated Single Up to 11kV 15 22
Multicore Up to 11kV 12 18
Single Core 22kV 18 27
Multicore 22kV 15 22
Single Core 33kV 20 30
Multicore 33kV 18 27
Trailing Elastomer
(1) Single and Multicore 1.1kV 6
(2) Single and Multicore 3.3kV & above 12
Welding PVC or Elastomer 0.6/1kV 6
Nylon Covered All Cables 20 30
HDPE Sheathed All Cables 15 25

Factor x cable overall diameter = minimum internal bending radius.